YXZ2V-U, YXZ2V-R, N2XRY

Place of use

These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage. 

Structure

1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath. 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-43000001 1x1.5 10.5 200 1000 12.1 39 32
28-43000002 1x2.5 11.0 220 1000 7.41 51 42
28-43000003 1x4 11.5 250 1000 4.61 66 56
28-43000004 1x6 12.0 280 1000 3.08 82 71
28-43000005 1x10 13.0 350 1000 1.83 109 96
28-43000006 1x16 14.0 450 1000 1.15 139 128
28-43000007 1x25 15.5 550 1000 0.727 179 173
28-43000008 1x35 17.5 800 1000 0.524 213 212
28-43000009 1x50 19.0 1000 1000 0.387 251 258
28-43000010 1x70 20.5 1250 1000 0.268 307 328
28-43000011 1x95 23.0 1700 1000 0.193 366 404
28-43000012 1x120 25.0 2000 1000 0.153 416 471
28-43000013 1x150 26.5 2350 1000 0.124 465 541
28-43000014 1x185 28.5 2800 1000 0.0991 526 626
28-43000015 1x240 31.5 3450 1000 0.0754 610 749